Determination of Dissolved Gas Limits in Insulating Oil of Vacuum on-Load Tap Changer in Power TransformersDetermination of Dissolved Gas Limits in Insulating Oil of Vacuum on-Load Tap Changer in Power Transformers
DOI:
https://doi.org/10.5281/zenodo.13208915Keywords:
On-load tap changer, dissolved gas, duval triangle, outlier.Abstract
In power transformers, which are widely used in the electricity transmission system, voltage adjustment is performed by means of on-load tap changers (OLTC). One of the commonly used types of on-load tap changers is vacuum type on-load tap changers. In vacuum type on-load tap changers, while tap-changing under load, flammable gases occur in the insulating oil inside the tap changer chamber due to malfunction of vacuum tubes, mechanical breakdowns or fixed and movable bypass contact switches in the oil. Failure detection can be made with limit values and analysis methods determined by looking at the types and amounts of these flammable gases. In this study, vacuum, resistance and separate compartment (VRS) type, on-load tap changers used in power transformers of Turkish Electricity Transmission Corporation (TEİAŞ) are discussed. The warning limits of gases dissolved in mineral oil in these VRSs are determined by using the outlier analysis method in IEEE C57.139 standard. In addition, the N1 region within the X1 region for these OLTCs in the duval triangle2 is determined as the normal operating region.
References
ABB Power Technologies, Dissolved gas analysis in on-load tap-changer oil, Info Sheet No. lZSC000498-AAAen, ABB,2004.
Al-Ameri, S. M., Almutairi, A., Kamarudin, M. S., Yousof, M. F. M., Abu-Siada, A., Mosaad, M. I., & Alyami, S. (2021). Application of frequency response analysis technique to detect transformer tap changer faults. Applied Sciences, 11(7), 3128).
Analysis of Gases Dissolved in Electrical Insulating Oil by Gas Chroma-tography, ASTM D 3612-02, 2009.
CIGRE. Advances in DGA Interpretation; JWG D1/A2.47. Technical Brochure No. 771; CIGRE: Paris, France, 2019.
CIGRE. DGA in Non-Mineral Oils and Load Tap Changers and Improved DGA Diagnosis Criteria; WG D1.32.Technical Brochure No. 443; CIGRE: Paris, France, 2010.
Duval M., The Duval Triangle for Load Tap Changers, Non-Mineral Oils and Low Temperature Faults in Transformers, IEEE Electrical Magazine,2008.
Duval, M. (1974, January). Fault Gases Formed In Oil-Filled Breathing Ehv Power Transformers-Interpretation Of Gas-Analysis Data. In IEEE Transactions on Power Apparatus and Systems (No. 6, pp. 1745-1746). 345 E 47TH ST, NEW YORK, NY 10017-2394: IEEE
Frotscher, R., Shen D., Farell T., Dissolved Gas Analysis – Condition Monitoring of Vacuum Type Tap Changers for Power Transformers, CEPSI, Bangkok, 2016.
Frotscher, R., Tap-changer DGA: Uncovering an enigma, Part 2: Basic procedures, Transformers Magazine, Volume 4, Issue 4, pp. 20-26, October 2017.
Frotscher, R., Tap-changer DGA:Uncovering an enigma,Part1:The field of DGA, Transformers Magazine, Volume3 Issue4, pp. 22-27, July 2017.
Frotscher, R., Tap-changer DGA:Uncovering an Enigma; Part 3: Interpretation, Transformers Magazine Vol 5, Issue 1, 2018.
Hohlein I., Atanasova, R. Frotscher: Carbon Oxides in the Interpretation of Dissolved Gas Analysis in Transformers and Tap Changers, IEEE Electrical Insulation Ma gazine, Vol. 26, No. 6, 2010.
IEEE C.57.139,Guide for Disolved Gas Analysis in Transformer Load tap Changers, 2015.
Naderian A., An Approach to Determine the Health Index of Power Transformers,IEEE,2008.
Pan, Z., Zhang, J., Zhou, H., Deng, J., Liang, C., & Li, D. (2020, September). Mechanical Condition Assessment of Vacuum On-load Tap-changer for Converter Transformer based on time-frequency domain characteristics of Vibration Signal. In 2020 IEEE International Conference on High Voltage Engineering and Application (ICHVE) (pp. 1-4). IEEE
Sezer M.,Trafo Maintenance and Insulation Oil, Best, 2014.
Shen Dazhong, Axel Kraemer, Dieter Dohnal, "Application of vacuum on-load tap-changers in HVDC converter transformers," Southern Power System Technology, 5, pp. 25-28, 2011
Tenbohlen, S., Standardized Survey of Transformer Reliability,Conference Proceedings of ISEIM,2017.
Downloads
Published
Versions
- 2024-08-29 (2)
- 2024-08-05 (1)
How to Cite
Issue
Section
License
Copyright (c) 2024 International Journal of Sustainability
This work is licensed under a Creative Commons Attribution 4.0 International License.